a. Classes. Non-metallic waterstops shall be of the following
classes, as specified:
Class I shall be fabricated of either natural or synthetic rubber.
Class II shall be fabricated of vinyl chloride polymer or copolymer.
b. Types. Non-metallic waterstops may be either split or solid and
shall conform to the following types, as specified, (see figure 1):
Type A shall have ribbed anchor flanges and a smooth web. Flanges may
be of uniform thickness or may have either a converging or a diverging taper
toward the edges.
Type B shall have ribbed anchor flanges and a smooth web containing a
hollow tubular center bulb having: (1) a wall thickness equal to at least
one-half (1/2) the web thickness, and; (2) the inside diameter (D) specified
in the specifications or shown on the drawings. Flanges may be of uniform
thickness or may have either a converging or a diverging taper toward the
edges.
Type C shall have a single, circular bulb-type anchor flange at each
edge and a smooth web.
Type D shall have a single, circular bulb-type anchor flange at each
edge and a smooth web containing a hollow tubular center bulb having: (1) a
wall thickness equal to a least one-half (1/2) the thickness of the web,
and; (2) the inside diameter (D) specified in the contract.
Type E shall have ribbed anchor flanges and a web molded or extruded
in the form of a round or U-shaped bulb of the dimensions specified in the
contract or shown on the drawings. The web bulb shall be connected at the
open-end of the "U" by a thin membrane having a minimum thickness
of 1/64-inch and a maximum thickness of 1/5 of the web thickness and design
to: (1) prevent infiltration of wet concrete into the bulb, and; (2) tear
when expansion of the joint occurs. Flanges may be of uniform thickness or
may have either a converging or a diverging taper toward the edges.
Auxiliary positioning or nailing flanges may be provided as long as the
functioning of the web bulb is not altered.
Type F shall have ribbed anchor flanges with a minimum of two (2)
extra heavy ribs, designed to resist displacement of the waterstop during
concrete placement on each flange, and a smooth web having a positioning or
nailing flange attached at the center.
Type G shall be of special design conforming to the details shown on
the drawings.
c. Sizes. Waterstops of Types A through F shall be of the sizes
specified in the specifications or shown on the drawings and listed in Table
1 of this specification. Type G waterstops shall have the dimensions shown
on the drawings.